Download PDFOpen PDF in browser

Power Control Strategies of Grid Side Inverters Over Unbalanced Grid Faults in PMSG-Based Wind Turbines

EasyChair Preprint no. 2044

10 pagesDate: November 28, 2019

Abstract

The high level of penetration forces the wind turbines stay connected to the grid during the disturbances in order to enhance system stability. Requirements of grid codes for wind power integration will also be discussed regarding active power control, reactive power control and fault ride through (FRT) capability. For the MPPT, a proportional control loop is added to the torque control to reduce the influence of the inertia moment in the wind turbines, which can improve its dynamic performance. Furthermore, the grid side active power oscillation and dc-link voltage ripple can be suppressed by using the proposed controller. In this system, the entire control system by using proportional resonant controller to reduce the computational time. Simulation results showed the validity and efficiently of the proposed control approach in different conditions.

Keyphrases: active power control, grid faults, low voltage ride through(LVRT), Maximum Power Point Tracking (MPPT)., peak current limitation, voltage sag

BibTeX entry
BibTeX does not have the right entry for preprints. This is a hack for producing the correct reference:
@Booklet{EasyChair:2044,
  author = {P Parvathee Devi and D Narmitha and G Lakshmi Lavanya},
  title = {Power Control Strategies of Grid Side Inverters Over Unbalanced Grid Faults in PMSG-Based Wind Turbines},
  howpublished = {EasyChair Preprint no. 2044},